STUB-800

            

ALL - IN - ONE STERILE CONDITIONING UNIT 

Product Specification : STUB - 800

 

Indoor Unit

Casing                      : Double Skin Panel 25 mm. , PS Foam Insulation

Supply Fan               : Plug fan with direct drive motor.

Air Flow Rate            : 600 -1200 CMH.

Cooling Capacity       : 24,000 BTU/hr.

Heating                   : 24,000 BTU/hr.

Cooling Coil              : Plate Fin Aluminum.

Reheat Coil              : Plate Fin Aluminum.

Drain Pan                : Stainless Steel 304

Filtration                  : Pre Filter 20 - 25%

                                 Medium Filter 90 - 95%

                                 HEPA Filter 99.995% By DOP Method *1

Fresh Air Flow Rate   : 60 - 80 CFM., Create 10 Pascal Positive Pressure inside the room.

Control System         : DDC Controller

*The Sterile Air Conditioner does not support DOP Testing (Leak test) Base on GMP Standards due to slight leakage at time of product installation

 

Dimension

 

 

Outdoor


Cooling Capacity       : 24,000 BTU/hr.

Compressor              : Scroll type

Power Supply           : 220 VAC. 50 Hz. Single Phase.

Power Input             : 2.2 kw.

Current                    : 10.30 Amps.

Refeigerant              : R - 32

 

Room Air change Per Hour


*Note

- Air change rate calculation base on room volume comparing with unit air flow performance This is not included another factor such as room air leakage/windown and door.

- **Room Hight 2.8 m.

 

Visitors: 54,600